Applying Power and Operation

Chapter 4

Bypass Switch Modes

The maintenance bypass switch has three modes of operation: Normal Mode,
Bypass Mode, and Test Mode. It is configured as shown in

Figure 9

.

Normal Mode

The NORMAL mode for the HC-DySC is the input circuit breaker (CBI) and
the output circuit breaker (CBO) closed. The bypass circuit breaker (CBB) must
be open or the HC-DySC will not be able to correct voltage sags. There is a red
indicator light on the enclosure that is lighted when the bypass circuit breaker is
closed. The green "OK" status box should be shown on the touchscreen display.
The green "OK" box indicates that the voltage at the output of the HC-DySC is
within the +10%, -13% normal window. Refer to Table 2 for operational
conditions and indications

Bypass Mode

The BYPASS mode for the HC-DySC is for the input circuit breaker (CBI) and
the output circuit breaker (CBO) to be open. The bypass circuit breaker (CBB)
must be closed to provide power to the load while the HC-DySC is being
serviced.

Refer to

Maintenance Bypass Transfer Procedure on page 18

for instructions on

transferring the system into and out of bypass mode.

Figure 9 - Maintenance Bypass Switch Configuration.

WARNING: Servicing must only be performed by factory authorized and
qualified personnel