HC-DySC with Generator Transfer (GT) Option

Appendix A

Typical TB2 connections for a hardwired generator transfer command contact
signal are shown in

Figure 33

. The signal is connected between positions 1 and 2.

Position 1 provides 24VDC to a (normally closed) auxiliary contact on the ATS
or generator circuit, which is fed back to terminal 2. Open the external contact to
put the HC-DySC in GT mode. An internal contact between Positions 3 and 4
closes whenever the HC-DySC is in the GT mode. This is a remote indicator
that the HC-DySC is in GT Mode. This contact is rated for 2A and 24V. Note:
if the HC-DySC 24V supply is used to power a remote indication device the
device must not exceed 15 W. To place the HC-DySC permanently in GT mode:
open the connection between TB2 positions 1 and 2.

Position 5 provides the 24V return, which is internally connected to chassis
ground. If an optional READY indicator is installed, connect all 24V returns
together when multiple HC-DySC units are installed, as shown in

Figure 34

.

ATTENTION: TB2 Recommended torque is 8 lb.-in. (0.9 N-m). Acceptable wire sizes are 22...8
AWG.

Figure 33 - Typical TB2 ATS / Generator Communication Connections

Figure 34 - Typical TB2 ATS/Generator Communication Connections (Multiple HC-DySC Units)

USER

PROVIDED

K

Located at ATS

+

Optional

+24VDC

GT Command

Ready
Indicator

GT Ready

TEST

Optional

Note: Contact K must open at least 1s before

ATS transfers to emergency power

HC-DySC

+24VDC
GT Command

24VDC Return

Closes in
GT Mode

EARTH GROUND

TB2

1

6

5

4

3

2

USER

PROVIDED

K

Located at ATS

+

Optional

+24VDC

Ready
Indicator

GT Ready

TEST

GT Ready

Chain

Chain

24VDC Return

GT Command

HC-DySC 1

+24VDC
GT Command

24VDC Return

Closes in
GT Mode

EARTH GROUND

TB2

1

6

5

4

3

2

HC-DySC 2

+24VDC
GT Command

24VDC Return

Closes in
GT Mode

EARTH GROUND

TB2

1

6

5

4

3

2

Note: Contact K must open at least 1s before

ATS transfers to emergency power