Rockwell Automation Publication 1608P-UM005A-EN-P - November 2014

Chapter 6

Maintenance

36

COM_VER

Start-Up Test: Communication
Compatibility Mismatch

Call Service

Unit

Firmware communication compatibility problem detected during start-up
test.

Call service.

37

CNFG_TO

Start-Up Test: Controller
Configuration Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

38

CNFG_ERR

Start-Up Test: Controller
Configuration Mismatch

Call Service

Unit

Controller firmware configuration problem detected during start-up test.

Call service.

39

FIRM_TO

Start-Up Test: Controller Firmware
Check Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

40

FIRM_DIFF

Start-Up Test: Controller Firmware
Revision Mismatch

Call Service

Unit

Controller firmware revision mismatch detected during start-up test.

Call service.

41

SRL_TO

Start-Up Test: Controller Serial
Number Check Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

42

SRL_DIFF

Start-Up Test: Serial Number
Mismatch

Informational

Unit

Controller serial number mismatch detected during start-up test.

No action needed.

44

T_INV_TO

Inverter Test Timeout

Call Service

Unit

Phase control board failed to respond to Comm board's Inverter test.

Call service.

47

CRIT_OT

Critical Over-Temperature

Manual Reset

Unit

Internal DySC temperature exceeded maximum rating. Mechanical bypass
commanded.

Verify ambient temperature is within DySC specification.
Check for damaged fans. Check for dirty or obstructed air filters.
Manually reset DySC.

48

FUSE_OPEN

Fuse Open

Call Service

Unit

One of the DySC fuses was detected open. Mechanical bypass commanded.

Call service.

49

OPEN_SCR_A

Open SCR Phase A

Call Service

Static Switch

The SCR on the phase A module was detected open.

Call service.

50

OPEN_SCR_B

Open SCR Phase B

Call Service

Static Switch

The SCR on the phase B module was detected open.

Call service.

51

OPEN_SCR_C

Open SCR Phase C

Call Service

Static Switch

The SCR on the phase C module was detected open.

Call service.

53

DYN_BRAKE

Dynamic Brake Error

Call Service

Unit

A problem was detected with the DySC dynamic brake controller.

Call service.

58

PLC_ERR

Programmable Logic Controller
Error

Call Service

PLC

PLC error detected.

Call service.

59

PLC_ST_MM

Programmable Logic Controller
State Mismatch

Call Service

Unit

PLC feedback error detected.

Call service.

73

INPUT_PS_FAIL

Input Control Power Supply Failure

Call Service

Unit

System output control power supply is not operating properly.

Call service.

74

OUTPUT_PS_FAIL

Output Control Power Supply
Failure

Call Service

Unit

System output control power supply is not operating properly.

Call service.

Event

Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution