Chapter 2

Installation

Floor Mounting

Secure the HC-DySC to the floor using fasteners and fittings appropriate for the
type of floor. Holes are provided in the base channels; see

Figure 1

for mounting

dimensions.

Note: Top or bottom cable entry is allowed. See

Figure 1

and

Figure 2 on page 9

.

Figure 1 - Bottom View Floor Mount Dimensions

Clearance

HC-DySC doors hinge on both right and left. See

Figure 30 on page 40

for

dimensions including door swing. Leave required clearances:

Door swing must allow doors to open at least 90°

3”[75 mm] on right side for air filter clearance when the door is open

Left side clearance is required for bottom entry cable installation

Circuit Breaker
Recommendations

Branch circuit protection upstream of the HC-DySC is required. Maximum
allowed circuit breaker ratings are listed in

Table 1

. Branch circuit protection that

is rated less than the HC-DySC current rating may result in nuisance tripping.

Table 1 - Branch Circuit Protection Ratings

1.38

35

1.00

25

1.20

31

6X

.625

16

2.01

51

9.00

229

11.00

279

3.58

91

37.25

946

28.00

711

37.25

946

18.75

476

Removable Plate for

Bottom Conduit Entry

HC-DySC Rating

Max. MCCB Rating

200 A

250 A

WARNING: To reduce the risk of fire, use only on circuits that are provided with
250 ampere maximum branch circuit protection in accordance with the
National Electric Code ANSI/NFPA 70.