10 ControlNet Fiber-optic Ring Repeater Modules

Rockwell Automation Publication 1786-IN003D-EN-P - April 2011

Fiber-optic Ring Topology

Use this configuration for long distances. A fiber-optic ring may contain as many
as 20 member modules. These member modules (four shown in

Figure 2

)

include the following:

1786-RPA/B repeater adapter module
1786-RPFRL/B long-distance ring repeater module
1786-RPFRXL/B extra long-distance ring repeater module

Figure 2 - Fiber Ring Topology Example

TIP

You cannot exceed 20 repeater modules in a series. If a ring is
broken, whether accidentally or on purpose for testing, the
configuration then becomes linear and the number of repeaters
depends on where the ring is broken. Most likely you will have as
many repeaters as in the original ring, such as the four shown in
Figure 2.

1786-RPA

1786-RPFR(X)L

1786-RPFR(X)L

1786-RPA

CH1

CH2

CH1

CH2

1786-RPA

1786-RPFR(X)L

1786-RPA

1786-RPFR(X)L

CH1

CH2

CH1

CH2

Rx

Tx Rx

Tx

Rx

Tx

Rx

Tx

Rx

Tx

Rx

Tx

Rx

Tx

Rx

Tx

1794-ACNR15

1794-ACNR15

1794-ACNR15

31237-M

On all fiber repeater modules, the leftmost connector is the RX (Receive) port;
the rightmost connector is the TX (Transmit) port.