ControlNet Fiber-optic Ring Repeater Modules 31

Rockwell Automation Publication 1786-IN003D-EN-P - April 2011

Flashing red/off

Module is powered, but not
ready for operation. This
state should also occur
during module reset and last
for approximately
5 seconds.

Do nothing. The fiber
repeater module is
operating properly.

Intermittent red

As more data errors are
detected the frequency of
the flashing red increases
until a solid red displays.

Check for proper operation.

Red

Excessive receive signal
distortion.

Review these items:

Be certain that you are

using the correct fiber
type for your module.

Check fiber length and

attenuation to make sure
that it is within
specification.

Replace the downstream

1786-RPFRL module on
the channel that is
having the intermittently
flashing red status
indicator.

Be certain that your total

network length is not out
of specification.

Be certain that SMAX is

correctly defined in the
RSNetWorx for
ControlNet software.

Table 3 - Fiber Repeater Module Status Indicators

If the fiber repeater
module indicator is

This means

You should