8. Reinsert the power supply connector into the 1786-RPA/B module.

Install the Ferrite at the Relay Contact Connector

1. Use the key to open the remaining ferrite.
2. Form a loop with both wires (+ and -) approximately 100 mm (4.0 in.)

away from the relay contact connector of the 1786-RPFRL/B or
1786-RPFRXL/B module.

3. Loop the wires through the ferrite.
4. Close the ferrite.

Be careful not to damage the wires.

5. Strip approximately 6 mm (0.24 in.) of wire from the end that will

connect to the relay contact connector on the 1786-RPFRL/B or
1786-RPFRXL/B module.

6. Remove the relay contact connector from the 1786-RPFRL/B or

1786-RPFRXL/B module.

7. Install the stripped ends of the wires in the relay contact connector on

the fiber repeater module as shown below.

8. Reinsert the relay contact connector into the 1786-RPFRL/B or

1786-RPFRXL/B module.

Connect the Ferrite Here