Specifications – Rockwell Automation 1786-RPFRXL ControlNet Fiber Ring Modules Installation Instructions User Manual

Page 33

Advertising
background image

ControlNet Fiber-optic Ring Repeater Modules 33

Rockwell Automation Publication 1786-IN003D-EN-P - April 2011

Specifications

Technical Specifications - 1786-RPFRL/B, 1786-RPFRXL/B

Attribute

1786-RPFRL/B, 1786-RPFRXL/B

All supply voltages or voltage ranges

Input: 570 mA @ 5V DC, max
Relay: 900 mA @ 30V DC, max resistive

Backplane power requirements

2.8 W (3.02 W, max)

(1)

(1)

Operational power is provided from the 1786-RPA/B module. For application within the U.S., supply
the 1786-RPA/B module from a power supply that is appropriately certified Class 2 per the definition
in the National Electrical Code, ANSI/NFPA 70, Article 725. For applications outside the U.S., supply
the 1786-RPA/B module from a safety extra low voltage (SELV) power supply. SELV output is built with
appropriate isolation to withstand single fault conditions. The output cannot exceed 30V rms, 42.4V
peak, or 60V DC under fault conditions.

Communication rate

5 Mbps

Mounting orientation

Any mounting orientation

Relay contact connector voltage

30V DC, max

Relay contact connector current
consumption

1 mA, min; 900 mA, max

Relay contact load type

Resistive only

Isolation voltage

50V (continuous), Basic insulation type,
Relay contacts to system

Optical power budget

See the optical power budget table
on

page 19

Wire size

0.25... 2.5 mm

2

(22...14 AWG) solid or

stranded copper wire rated at 75 °C
(167 °F ), or greater, 1.2 mm (3/64 in.)
insulation max for relay connections

Wiring category

2 - on signal ports

(2)

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Enclosure type rating

None (open-style)

North American temp code

T5