Rockwell Automation 1734-IM2_IM4 POINT I/O 220V AC Input Module User Manual

Page 20

Advertising
background image

20 POINT I/O 220V ac Input Module

Publication

1734-IN008C-EN-E - January 2007

Solid Red

Unrecoverable fault may require device
replacement.

Replace device.

Flashing
Red/Green

Device is in self-test.

None.

Network Status

Off

Device is not online.
- Device has not completed dup_MAC_id
test.
- Device not powered - check module
status indicator.

Apply power to device,
wait for MAC_id to
complete, and correct, as
needed.

Flashing Green

Device is online but has no connections
in the established state.

None - device is in Idle or
Program mode.

Solid Green

Device online and has connections in the
established state.

None.

Flashing Red

One or more I/O connections in timed-out
state.

Check for I/O module
failure, and correct, as
needed.

Solid Red

Critical link failure - failed
communication device. Device detected
error that prevents it communicating on
the network.

Verify that adapter and
terminal bases are
properly installed, and
reinstall, as needed.

Flashing
Red/Green

Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identify Communication Faulted
Request - long protocol message.

Verify that adapter is
properly installed, and
reinstall, as needed.

I/O Status

Off

Input is in the off-state.

None.

Solid Yellow

Input is in the on-state.

None.

Interpret the LED Indicators

State

Description

Recommended Action