Environmental Specifications

Attribute

Value

Temperature, Operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)

Temperature, Storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Shock, Operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

ESD Immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

EFT/B Immunity

IEC 61000-4-4:
±4 kV at 5 kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Emissions

CISPR 11 Group 1, Class A