North american hazardous location approval, Point i/o 220v ac input module 3 publication, Explosion hazard – Rockwell Automation 1734-IM2_IM4 POINT I/O 220V AC Input Module User Manual

Page 3: Risque d’explosion

Advertising
background image

POINT I/O 220V ac Input Module 3

Publication

1734-IN008C-EN-E - January 2007

North American Hazardous Location Approval

The following information applies when
operating this equipment in hazardous
locations.

Informations sur l’utilisation de cet équipement
en environnements dangereux.

Products marked CL I, DIV 2, GP A, B, C, D are suitable for
use in Class I Division 2 Groups A, B, C, D, hazardous
locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When
combining products within a system, the most adverse
temperature code (lowest “T” number) may be used to
help determine the overall temperature code of the
system. Combinations of equipment in your system are
subject to investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent
qu’à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa plaque
d’identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du
système. Les combinaisons d’équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées
au moment de l’installation.

EXPLOSION HAZARD -

• Do not disconnect equipment unless

power has been removed or the area
is known to be nonhazardous.

• Do not disconnect connections to

this equipment unless power has
been removed or the area is known
to be nonhazardous. Secure any
external connections that mate to
this equipment by using screws,
sliding latches, threaded
connectors, or other means provided
with this product.

• Substitution of components may

impair suitability for Class I, Division
2.

• If this product contains batteries,

they must only be changed in an
area known to be nonhazardous.

RISQUE D’EXPLOSION –

• Couper le courant ou s’assurer que

l’environnement est classé non
dangereux avant de débrancher
l'équipement.

• Couper le courant ou s'assurer que

l’environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous les
connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou
autres moyens fournis avec ce
produit.

• La substitution de composants peut

rendre cet équipement inadapté à une
utilisation en environnement de
Classe 1, Division 2.

• S’assurer que l’environnement est

classé non dangereux avant de
changer les piles.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use
zinc plated, yellow-chromate steel DIN rail to be sure of proper
grounding. The use of other DIN rail materials, such as aluminum and
plastic, which can corrode, oxidize, or are poor conductors, can result
in improper or intermittent grounding. Secure DIN rail to mounting
surface approximately every 200 mm (7.87 in.) and use end-anchors
appropriately.

WARNING

AVERTISSEMENT

Advertising