220V ac Input Modules - 1734-IM2 and 1734-IM4

Attribute

Value

Number of Inputs

1734-IM2: 2 (1 group of 2) nonisolated, sink
1734-IM4: 2 (1 group of 4) nonisolated, sink

On-state Voltage Range,
Min

159V ac

On-state Voltage Range,
Nom

220V ac

On-state Voltage Range,
Max

264V ac

On-state Current, Min

6.2 mA @ 159V ac, 60 Hz

On-state Current, Nom

8.5 mA @ 220V ac, 60 Hz

On-state Current, Max

10.2 mA @ 264V ac, 60 Hz

Off-state Voltage, Max

43V ac

Off-state Current, Max

2.9 mA

Input Impedance, Nom

22.3 k

Ω

Delay Time

(1)

Off to On and On to Off

(1)

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input
on-to-off filter time is the time from the input signal dropping below the valid level to recognition by
the module. Due to the randomness of the ac line cycle measurement capture point and response time
of the hardware filter, the maximum hardware delay is 20 ms plus the filter time.

20 ms hardware filter plus 1…64 ms digital filter
programmable in increments of 1 ms