3 - preliminary operating considerations, Module id code, Chapter 3 – Rockwell Automation 1746-NO8V SLC 500 8-Point Analog Output Module/ User Manual User Manual

Page 21: Preliminary operating considerations, Module id code -1, Chapter

Advertising
background image

1

Publication 1746-UM026A-EN-P - September 2003

Chapter

3

Preliminary Operating Considerations

This chapter explains how the analog output module and the SLC 500
processor communicate through the module’s input and output image.
It lists the preliminary setup and operation required before the
module can function in a 1746 I/O system. Topics discussed include
how to:

enter the module ID code

select the Class 1 or Class 3 interface

interpret communication between the SLC processor and the
output module

calculate the module update time

interpret the module response to slot disabling

Module ID Code

The module identification code is a unique number encoded for each
1746 I/O module. The code defines for the processor the type of I/O
or specialty module residing in a specific slot in the 1746 chassis.

Table 3.1 1746-NO8 Module ID Codes

Catalog Number

ID Code

1746-NO8I

Class 1 interface 3527

Class 3 interface12727

1746-NO8V

Class 1 interface 3528

Class 3 interface 12728