Rockwell Automation 1746-NO8V SLC 500 8-Point Analog Output Module/ User Manual User Manual

Page 44

Advertising
background image

Publication 1746-UM026A-EN-P - September 2003

4-20 Configuring the Module

]/[

I:1.8

2

OTHER

] [

I:1.8

1

OTHER

0001

MOV

MOVE
Source

10000
10000

Dest

O:1.24

10000

<

<

CH0_PARAMETER2

MOV

MOVE
Source

5905
5905

Dest

0:1.8
4113

<

<

CH0_CONFIG

MOV

MOVE
Source

5000
5000

Dest

O:1.16

5000

<

<

CH0_PARAMETER1

CH0_CLAMPING_SET

CH0_LIMIT_AL_SET

The rung below configures Channel 0 for 0 to 21 mA, sets the alarm limit range from 5000 to 10000, and holds the output in its last state on a fault
condition.
Note: 5905 decimal = 0001 0111 0001 0001 binary.

]/[

I:1.8

2

OTHER

] [

(END)

I:1.8

1

OTHER

0002

0003

MOV

MOVE
Source

4113
4113

Dest

O:1.8

4113

<

<

CH0_CONFIG

CH0_CLAMPING_SET

CH0_LIMIT_AL_SET

I:1.8/2 --> CH0_LIMIT_AL_SET

The rung below configures Channel 0 for 0 to 21 mA, sets the parameter option to “no action”, and holds the output in its last state on a fault
condition. Note: 4113 decimal = 0001 0000 0001 0001 binary.