Ladder program to configure channel 0, Ladder program to configure channel 0 -19 – Rockwell Automation 1746-NO8V SLC 500 8-Point Analog Output Module/ User Manual User Manual

Page 43

Advertising
background image

Publication 1746-UM026A-EN-P - September 2003

Configuring the Module 4-19

Ladder Program to
Configure Channel 0

]/[

I:1.8

1

OTHER

0000

MOV

MOVE
Source

20000
20000

Dest

O:1.24

10000

<

<

CH0_PARAMETER2

MOV

MOVE
Source

5393
5393

Dest

0:1.8
4113

<

<

CH0_CONFIG

MOV

MOVE
Source

4000
4000

Dest

O:1.16

5000

<

<

CH0_PARAMETER1

CH0_CLAMPING_SET

The rung below configures Channel 0 for 0 to 21 mA, sets the clamping range from 4000 to 20000, and holds the output in its last state on a fault
condition.
Note: 5393 decimal = 0001 0101 0001 0001 binary.