How the SLC Processor
Communicates with the
Module

The SLC processor transfers data to (and receives data from) the
output module through an image table residing in the data files of the
SLC processor. The processor updates this image table once during
each scan of the ladder program. Figure 4 shows the image table for
your output module.

Figure 3.1 Output and input scans

Channel Update Time

For an output module, channel update time is the time required for
the module to convert the channel data received from the processor to
an analog output signal at the terminals.

The channel update time varies depending upon mode of operation
and features implemented. Class 1 and Class 3 update times are
shown below:

SLC 500
Data Files

Module
Image Table

Slot e

Input Image

Slot e

Output Image

Output Image:
8 words Class 1
32 words Class 3

Input Image:
8 words Class 1
16 words Class 3

Table 3.3 1746-NO8 Channel Update Time (all channels)

Mode of Operation

Update Time

Class 1

5 ms

Class 3

10 ms