Publication 1746-UM026A-EN-P - September 2003

Replacing 1746-NO4s with 1746-NO8 B-3

Channel Status Words

In Class 1 mode, the 1746-NO8 provides one status input word per
channel which is not available with the 1746-NO4. Consideration
should be given to implementation of user program logic to monitor
the status when converting from the 1746-NO4 module.

The Channel Status Words are addressed as follows:

In Class 1 mode, each channel status word contains the following
useful status information:

Bits 1 through 11 provide additional status information when Class 3
mode is configured. For more definition of status word bit use, refer
to Chapter 4.

Table B.3 1746-NO8V and 1746-NO4V Output Range

Voltage Range

Decimal Representation for
Output Word

Resolution per LSB

-10 to +10V dc

-32,768 to +32,764

1.22070 mV

0 to 10V dc

0 to 32,764

0 to 5V dc

0 to 16,384

1 to 5V dc

3,277 to 16,384

1746-NO8 Status Word Addressing

I:3.0 - Slot 3, Channel 0 Status Word

I:3.4 - Slot 3, Channel 4 Status Word

I:3.1 - Slot 3, Channel 1 Status Word

I:3.5 - Slot 3, Channel 5 Status Word

I:3.2 - Slot 3, Channel 2 Status Word

I:3.6 - Slot 3, Channel 6 Status Word

I:3.3 - Slot 3, Channel 3 Status Word

I:3.7 - Slot 3, Channel 7 Status Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Fatal Channel Error (0 = OK, 1 = error)

Module/SLC Resetting (0 = OK, 1 = reset)

Current Loop Open (0 = OK, 1 = open)

24V Power Failure (0 = OK, 1 = failure)

Channel Enabled (0 = off, 1 = on)