4-4

SA500 Power Modules

Step 2. Connect the DC bus wires (POS, NEG, GND) from the DC Bus Supply to the

Power Module. See figure 4.2.

The proper DC bus connection wires are provided with the Bus Supply. Do
not substitute other wires for those supplied.

Do not over-tighten the nuts on the Power Module and DC Bus terminals.
Use a nut-driver only and limit the torque to 4.0 Nm (36 lb-in).

Step 3. Connect the motor wires to the Power Module’s terminals (U,V,W). See

table 4.1.

Step 4. Apply power to the input wiring of the DC Bus Supply and check the bus

voltage. It should be 325 VDC nominal. Be sure the bus voltage is present at
the Power Module’s input terminals.

!

ATTENTION: To avoid the danger of an electrical shock or burn, only
qualified personnel should install or service this equipment. Disconnect
all power before working on this equipment. Dangerous voltages may
exist after power is removed. Check the DC Bus Supply voltages each
time power is removed before servicing. Failure to observe this
precaution could result in severe bodily injury or loss of life.

Table 4.1 – Recommended Motor Wire Sizes

SA500 AC

Power Modules

Motor Terminals

Minimum

1

/Maximum

2

Wire Sizes

1. Minimum wire size required.
2. Maximum wire size allowed.

615055-1R

U-V-W,GND

4.8 / 21.6 mm

2

10 / 4 AWG

615055-1S

U-V-W,GND

4.8 / 21.6 mm

2

10 / 4 AWG

615055-1T

U-V-W,GND

8.5 / 21.6 mm

2

8 / 4 AWG

615055-1V

U-V-W,GND

13.7 / 21.6 mm

2

6 / 4 AWG