Status of Data in the AutoMax Rack After a STOP_ALL Command or STOP_ALL Fault

E-1

A

PPENDIX

E

Status of Data in the AutoMax Rack

After a STOP_ALL Command or

STOP_ALL Fault

AutoMax Processor

UDC Module

PMI Processor

LOCAL tunable variables

retained

retained

retained

LOCAL variables

retained

reset to 0

N/A

COMMON memory variables

non-volatile are
retained;
others are reset to 0

N/A

N/A

I/O variables
(including UDC dual port memory

inputs retained and
updated;
outputs are reset to 0

see below

all I/O is reset to 0

Input values, including:

Feedback registers
UDC/PMI communication status
registers
UDC Error Log info

retained

retained

N/A

Output values, including:

Command registers
Application registers
ISCR registers
Scan-per-interrupt register
Scans-per-interrupt counter

reset to 0

reset to 0

N/A

Parameter configuration variables

N/A

retained

N/A

UDC test switch information

N/A

retained

N/A

D/A setup configuration

N/A

retained

N/A

Operating system

retained

retained

retained