Rockwell Automation AADvance Controller Troubleshooting and Maintenance Manual User Manual

Page 31

Advertising
background image


Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:

3-9

1. If Healthy is GREEN and all the other indicators are OFF then the
module has failed to boot up

2. If Healthy is GREEN and the Ready and Run are RED then the

module is said to be in its shutdown state ( See topic - Module Shutdown
State and Possible Causes in the Troubleshooting Manual Chap 3).

Ready

Provides an indication of the module's education and synchronisation

status

OFF

No power

RED

Module is booting up (10 to 20 seconds) or not educated or synchronised
with partners

GREEN

Module is educated and synchronised with partners

Flashing GREEN Education or synchronisation is in progress (may be a very short period of

flashing then Green)

Amber

Module is in the Recovery Mode

Run

Provides an indication of the module's application status. Should be the
same for all educated and synchronised processors

OFF

No power and stays off while the module is booting up (10 to 20 seconds)

RED

Module is not educated/synchronised; No application loaded; The
processor module is in the Recovery Mode and the base level firmware is

running

GREEN

The application is present and running

AMBER

Module is in the Recovery Mode

or

The application is present but not running, press Fault Reset to start it
running.

System Healthy

Provides an indication of the global health of the system, including all

processors and I/O modules. Must be the same indication for all educated
and synchronized processors

OFF

No power and stays off while the module is booting up (10 to 20 seconds)

RED

System or module faults present

or the application has stopped running because the module has entered
the Recovery Mode.

GREEN

No system or module faults present during normal operation and when in
the recovery Mode.

Force

Provides an indication that variables are being locked/forced by the

application. The same indication will show for all educated and
synchronised processors

OFF

No power and stays off while the module is booting up (10 to 20 seconds)

GREEN

No variables are being locked/forced

AMBER

Module is in the Recovery Mode.

or

Advertising