When a fault exists on a channel, the module will report safe values for that channel and the
Discrepancy status variable reports TRUE.

Simplex Module Configuration

When a simplex module channel fault exists for longer than the module PST the channel indicates a
fault condition and the following status values are reported:

Channel State = 7

Channel Input State = FALSE

Line fault = TRUE

Discrepancy = TRUE

Channel fault = TRUE

Channel reports a voltage value = 0

Dual Module Configuration

When the reported values between modules in digital/analogue modules of a dual configurations
diverge by more than twice the safety margin specification for a period of two application scans, that is
by the following values:

Digital input modules diverge by more than 2.0V dc

Analogue input modules diverge by 400µA.

the lower of the two values will be reported and a discrepancy flag is set and the configuration
degrades to a simplex operation.

Triple Module Configuration

When the reported values between modules in digital/analogue triple configuration diverge by more
than twice the safety margin specification for a period of two application scans, that is by the following
values:

Digital input module by more than 2.0V dc

Analogue input module by 400µA.

the lower of the two values will be reported and a discrepancy flag is set and the configuration
degrades to a dual operation.

Output Channel Shutdown

In shutdown mode the output module drives its outputs to their configured shutdown settings; for
example, de-energized or hold last state. The shutdown mode and channel drive states remain in place
until new command states are received from a running application, or until the module loses power.