Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:

4-11

You can do the following with an on-line update:

Change application variables or the program.

Add new I/O base units, termination assemblies and extra I/O modules.

Delete modules from the system.

Change the size of a termination assembly to change the size of the I/O
module configuration.

Move a module to a different slot.

Important Note: If you change the internal I/O configuration in the Workbench but fail to carry out
the same hardware changes the application will be stopped and the Run LED on the affected modules
will go RED.

Follow this on-line update process:

1) Do the hardware changes if changing the hardware I/O configuration.

2) Insert the Program Enable Key.

3) Select the resource and the Equipment tree view.

4) Do the changes to the I/O configuration.

5) Save the change.

6) Select the Build Project Library button

to compile the application.

7) Select the On-line Change: Download button

to do an on-line update.

The application is now downloaded to confirm the configuration change.

The system will shutdown each module deleted during an on-line update and
the Run LED will go RED.

A single module or the first module in a group will start up and educate and
the Run LED on the affected modules will go AMBER when the on-line change
is completed.

8) Press the Fault Reset button on the processor module to bring the modules fully

operational and the Run LED will go GREEN.

9) When 2

nd

or 3

rd

modules in a group are installed they will automatically educate

from the first module and go on-line.