Processor module start up process – Rockwell Automation AADvance Controller Troubleshooting and Maintenance Manual User Manual

Page 51

Advertising
background image


Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:

4-7

Processor Module Start Up Process

Note: When inserting more than one processor module they MUST be inserted one at a time and the
module be allowed to educate (in the case of a 2

nd

and 3

rd

processor).

Table 4:

Single Processor Module Installation Procedure (New Processor Module)

Step Task

1.

Install the processor into a processor base unit slot.

2.

All LEDs are off and after applying power the processor will display the following status
indications:

Healthy

Flashes RED for a second then goes GREEN as the module boots up (10
to 20 seconds)

Ready

Will remain OFF as the module boots up (10 - 20 seconds) then goes RED

Run

Will remain OFF as the Module boots up (10 to 20 seconds) then goes

RED

System Healthy Will remain OFF as the Module boots up (10 to 20 seconds) then goes

GREEN

Force

Will remain OFF as the Module boots up (10 to 20 seconds) then stays
OFF until the module has educated.

Aux

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection.

Serial 1

Will remain OFF as the Module boots up (10 to 20 seconds) then is

dependent upon data connection

Serial 2

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection

Ethernet 1

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection

Ethernet 2

Will remain OFF as the Module boots up (10 to 20 seconds) then is

dependent upon data connection

You have to set up the processor IP Address so that the workstation can communicate with the
processor module and download the latest firmware build and configure the processor variables.

3.

Set the Controller IP Address for all the processor modules using the "AADvance Discover
Utility". (Refer to the Configuration Guide for detailed instructions on using the AADvance

Discover Utility Doc. No: 553633.

4.

Install a Program Enable Key. Download a valid application and press the FAULT RESET
button. When the application is downloaded and valid the module will display the following

indications:

Valid Application Downloaded

Healthy

GREEN

Advertising