Rockwell Automation AADvance Controller Troubleshooting and Maintenance Manual User Manual

Page 33

Advertising
background image


Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:

3-11

Status Indicators on the T94xx Series Input and Output Module

Table 3:

Status Indicators on the 94xx Series Input and Output Module

Indicator

Status

Description

Healthy

Provides an indication of the general status of the module

OFF

No power

GREEN

No module faults present

RED

One or more module faults are present

Note.

1. The Healthy indicator may turn RED immediately upon application of
power to the module, before then turning GREEN

2. If Healthy is GREEN and the Ready and Run are RED then the
module is said to be in its "shutdown state" refer to the Troubleshooting
Manual - Chap 3 for more information on the shutdown state.

Ready

Provides an indication of the module's ability to report channel values to a
running application

OFF

No power or unlocked

GREEN

Locked and ready to report channel values

RED

Locked but not ready to report channel values

Run

Provides an indication that the module is reporting channel values to a
running application

OFF

No power or unlocked

GREEN

Module is online and providing data to/receiving data from application

AMBER

Module is inserted into a running system but not online. Press the Fault
Reset button on any processor module to enable the module to go online

RED

Module is ready to go online but no application is running

Channel 1 - 8

Provides an indication of the status of each input or output channel

OFF

Input module: field switch is open
Output module: output is in its de-energised state

If the run indicator is not green (the module is not reporting channel

Advertising