background image

13

4. Pressure--test all gas piping in accordance with local

and national plumbing and gas codes before connect-

ing piping to unit.

NOTE: Pressure test the gas supply system after the gas
supply piping is connected to the gas valve. The supply
piping must be disconnected from the gas valve during the

testing of the piping systems when test pressure is in
excess of 0.5 psig (3450 Pa). Pressure test the gas supply
piping system at pressures equal to or less than 0.5 psig
(3450 Pa). The unit heating section must be isolated from
the gas piping system by closing the external main manual

shutoff valve and slightly opening the ground--joint union.
Check for gas leaks at the field--installed and

factory--installed gas lines after all piping connections

have been completed. Use soap--and--water solution (or

method specified by local codes and/or regulations).

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury, death and/or property damage.
S

Connect gas pipe to unit using a backup wrench to

avoid damaging gas controls.

S

Never purge a gas line into a combustion chamber.

S

Never test for gas leaks with an open flame. Use a

commercially available soap solution made

specifically for the detection of leaks to check all

connections.

S

Use proper length of pipe to avoid stress on gas

control manifold.

!

WARNING

NOTE: If orifice hole appears damaged or it is suspected
to have been redrilled, check orifice hole with a numbered
drill bit of correct size. Never redrill an orifice. A

burr--free and squarely aligned orifice hole is essential for
proper flame characteristics.

BURNER

ORIFICE

A93059

Fig. 19 -- Orifice Hole

Step 11 — Install External Condensate Trap

and Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan and an alternate connection

on the bottom. See Fig. 20. Unit airflow configuration

does not determine which drain connection to use. Either

drain connection can be used with vertical or horizontal

applications.
When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do

this before setting the unit in place. The red drain pan can

be tightened with a

1

/

2

--in. square socket drive extension.

To use the alternate bottom drain connection, remove the

red drain plug from the bottom connection (use a

1

/

2

--in.

square socket drive extension) and install it in the side

drain connection.
The piping for the condensate drain and external trap can

be completed after the unit is in place. See Fig. 21.

DRAIN

(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARD

SIDE DRAIN

ALTERNATE

BOTTOM DRAIN

C08021

Fig. 20 -- Condensate Drain Pan (Side View)

NOTE: Trap should be deep enough to offset maximum unit static

difference. A 4” (102) trap is recommended

.

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

BASE RAIL

OPEN

VENT

TO ROOF

DRAIN

DRAIN PLUG

ROOF

CURB

SEE NOTE

2˝ (51) MIN

C08022

Fig. 21 -- Condensate Drain Piping Details

All units must have an external trap for condensate

drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed

downstream from the external trap, pitch the line away

from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do

not use a pipe size smaller than the unit connection
(

3

/

4

-in.).

581J