Bryant PURON 581J User Manual

Page 17

Advertising
background image

17

Units without Thru--Base Connections —

1. Install power wiring conduit through side panel open-

ings. Install conduit between disconnect and control

box.

2. Install power lines to terminal connections as shown

in Fig. 22.

Voltage to compressor terminals during operation must be

within voltage range indicated on unit nameplate. See

Table 5. On 3--phase units, voltages between phases must

be balanced within 2% and the current within 10%. Use

the formula shown in the legend for Table 5, Note 2 to

determine the percent of voltage imbalance. Operation on

improper line voltage or excessive phase imbalance

constitutes abuse and may cause damage to electrical

components. Such operation would invalidate any

applicable Bryant warranty.
Field Control Wiring —
The 581J unit requires an external temperature control

device. This device can be a thermostat emulation device

provided as part of a third--party Building Management

System.
Thermostat —
Install a Bryant--approved accessory thermostat according

to installation instructions included with the accessory.

For complete economizer function, select a two--stage

cooling thermostat. Locate the thermostat accessory on a

solid wall in the conditioned space to sense average

temperature in accordance with the thermostat installation

instructions.
If the thermostat contains a logic circuit requiring 24--v

power, use a thermostat cable or equivalent single leads of

different colors with minimum of seven leads. If the

thermostat does not require a 24--v source (no “C”

connection required), use a thermostat cable or equivalent

with minimum of six leads. Check the thermostat

installation instructions for additional features which

might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG

(American Wire Gage) insulated wire [35_C (95_F)

minimum]. For 50 to 75 ft. (15 to 23 m), use no. 16 AWG

insulated wire [35_C (95_F) minimum]. For over 75 ft.

(23 m), use no. 14 AWG insulated wire [35_C (95_F)

minimum]. All wire sizes larger than no. 18 AWG cannot

be directly connected to the thermostat and will require a

junction box and splice at the thermostat.

X

C

G

W2

C

W2

G

W1

O/B/Y2

Y2

R

W1

R

Y1

Y1

T
H
E
R
M
O
S
T
A
T

(Note 1)

(Note 2)

Note 1: Typical multi-function marking. Follow manufacturer’s configuration

Instructions to select Y2.

Note 2: Y2 to Y2 connection required on single-stage cooling units when

integrated economizer function is desired.

Field Wiring

Central

Terminal

Board

Typical

Thermostat

Connections

C08069

Fig. 28 -- Low--Voltage Connections

Unit without Thru--Base Connection Kit —
Pass the thermostat control wires through the hole

provided in the corner post; then feed the wires through

the raceway built into the corner post to the control box.

Pull the wires over to the terminal strip on the upper--left

corner of the Controls Connection Board. See Fig. 29.
NOTE:

If thru--the--bottom connections accessory is

used, refer to the accessory installation instructions for
information on routing power and control wiring.

RACEWAY

HOLE IN END PANEL (HIDDEN)

C08027

Fig. 29 -- Field Control Wiring Raceway

Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage

and 0.14 amp for second--stage heating, when available.

581J

Advertising