Table 3 – RTU Open Controller Inputs and Outputs

POINT NAME

BACnet OBJECT

NAME

TYPE OF I/O

CONNECTION PIN

NUMBER(S)

DEDICATED INPUTS

Space Temp / Zone Temp

zone_temp

AI (10K Thermistor)

J20---1, 2

Supply Air Temperature

sa_temp

AI (10K Thermistor)

J2---1, 2

Outdoor Air Temperature

oa_temp

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

stpt_adj_offset

AI (100K Potentiometer)

J20---3

Safety Chain Feedback

safety_status

DI (24 VAC)

J1---9

Compressor Safety Status

comp_status

DI (24 VAC)

J1---2

Fire Shutdown Status

firedown_status

DI (24 VAC)

J1---10

Enthalpy Status

enthalpy_status

DI (24 VAC)

J2---6

Humidistat Input Status

humstat_status

DI (24 VAC)

J5---7

CONFIGURABLE INPUTS

Indoor Air CO2

iaq

AI (4---20 ma)

J4---2 or J4---5

Outdoor Air CO2

oaq

AI (4---20 ma)

Space Relative Humidity

space_rh

AI (4---20 ma)

Supply Fan Status*

sfan_status

DI (24 VAC)

J5---1 or J5---3 or

J5 5 or J5---7

Filter Status*

filter_status

DI (24 VAC)

Door Contact Input*

door_contact_status

DI (24 VAC)

Occupancy Contact*

occ_contact_status

DI (24 VAC)

OUTPUTS

Economizer Output

econ_output

AO (4---20ma)

J2---5

Supply Fan Relay State

sfan

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

DO Relay (24VAC , 1A)

J1---7

Heat Stage 1 Relay State

heat_1

DO Relay (24VAC , 1A)

J1---6

Heat Stage 2 Relay State

heat_2

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

pexh

DO Relay (24VAC , 1A)

J11---3

Dehumidification Relay State

dehum

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

AI --- Analog Input

AO --- Analog Output

DI --- Discrete Input

DO --- Discrete Output

* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.

The RTU Open controller requires the use of a Bryant

space sensor. A standard thermostat cannot be used with

the RTU Open system.

Supply Air Temperature (SAT) Sensor —

On FIOP--equipped 581J unit, the unit is supplied with a

supply--air temperature (SAT) sensor (33ZCSENSAT).

This sensor is a tubular probe type, approx 6--inches (12.7

mm) in length. It is a nominal 10--k ohm thermistor.

The SAT is factory--wired. The SAT probe is wire--tied to

the supply--air opening (on the horizontal opening end) in

its shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a

1

/

2

--in. hole in the flange or duct.

Use two field--supplied, self--drilling screws to secure the

sensor probe in a horizontal orientation. See Fig. 36.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP or

accessory). It is a nominal 10k ohm thermistor attached to

an eyelet mounting ring.

SUPPLY AIR

RETURN AIR

SUPPLY AIR
TEMPERATURE
SENSOR

ROOF
CURB

C08200

Fig. 36 -- Typical Mounting Location for Supply Air

Temperature (SAT) Sensor on Small Rooftop Units