Bryant PURON 581J User Manual

Page 25

Advertising
background image

25

Connect T--59: The T--59 space sensor requires a

separate, isolated power supply of 24 VAC. See Fig. 41

for internal connections at the T--59. Connect the SEN

terminal (BLU) to RTU Open J20--1. Connect the COM

terminal (BRN) to J20--2. Connect the SET terminal (STO

or BLK) to J20--3.

OR

SET

SEN

OPB

COM- PWR+

BLU (SPT)

BLK (STO)

24 VAC

SENSOR
WIRING

POWER
WIRING

BRN (COM)

NOTE: Must use a separate isolated transformer.

J20-3

J20-2

J20-1

C10291

Fig. 41 -- Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Indoor Air Quality (CO

2

) Sensor —

The indoor air quality sensor accessory monitors space

carbon dioxide (CO

2

) levels. This information is used to

monitor IAQ levels. Several types of sensors are available,

for wall mounting in the space or in return duct, with and

without LCD display, and in combination with space

temperature sensors. Sensors use infrared technology to

measure the levels of CO

2

present in the space air.

The CO

2

sensors are all factory set for a range of 0 to

2000 ppm and a linear mA output of 4 to 20. Refer to the

instructions supplied with the CO

2

sensor for electrical

requirements and terminal locations. See Fig. 42 for

typical CO

2

sensor wiring schematic.

To accurately monitor the quality of the air in the

conditioned air space, locate the sensor near a return--air

grille (if present) so it senses the concentration of CO

2

leaving the space. The sensor should be mounted in a

location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near

supply ducts, open windows, fans, or over heat sources.

Allow at least 3 ft (0.9 m) between the sensor and any

corner. Avoid mounting the sensor where it is influenced

by the supply air; the sensor gives inaccurate readings if

the supply air is blown directly onto the sensor or if the

supply air does not have a chance to mix with the room air

before it is drawn into the return airstream.

8 7 6 5 4 3 2 1

2 1

H G 24 VAC

OR

24 VDC

NC

ALARM
RELAY
CONTACTS

COM
NO

}

0-10VDC
SIG COM

4-20mA

+

+

-

+ -

J3

J4

C08635

Fig. 42 -- Indoor/Outdoor Air Quality (CO

2

) Sensor

(33ZCSENCO2) -- Typical Wiring Diagram

Wiring the Indoor Air Quality Sensor: For each sensor,

use two 2--conductor 18 AWG (American Wire Gage)

twisted--pair cables (unshielded) to connect the separate

isolated 24 vac power source to the sensor and to connect

the sensor to the control board terminals.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

sensor. See Fig. 42. Connect the 4--20 mA terminal to

RTU Open J4--2 and connect the SIG COM terminal to

RTU Open J4--3. See Fig. 43.

SEN

COM

J4-2

J4-3

IAQ Sensor

24 VAC

C08462

Fig. 43 -- RTU Open / Indoor CO

2

Sensor

(33ZCSENCO2) Connections

Outdoor Air Quality Sensor

(PNO 33ZCSENCO2 plus weatherproof enclosure) —

The outdoor air CO

2

sensor is designed to monitor carbon

dioxide (CO

2

) levels in the outside ventilation air and

interface with the ventilation damper in an HVAC system.

The OAQ sensor is packaged with an outdoor cover. See

Fig. 44. The outdoor air CO

2

sensor must be located in the

economizer outside air hood.

581J