Caution – Bryant PURON 581J User Manual

Page 8

Advertising
background image

8

A-B

0.5” (13)

B-C

1.0” (25)

A-C

1.0” (25)

MAXIMUM ALLOWABLE

DIFFERENCE IN. (MM)

C06110

Fig. 4 -- Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition)

shall not exceed 0.35 in. wg (87 Pa) with economizer or

0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb

and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional

dimensions are equal to or greater than the unit supply

duct opening dimensions for the first 18 in. (458 mm) of

duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints,

and roof openings with counter flashing and mastic in

accordance with applicable codes.
Ducts passing through unconditioned spaces must be

insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return

should be ducted through the roof deck to comply with

applicable fire codes.

A minimum clearance is not required around ductwork.

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage

to roofing materials.
Membrane roofs can be cut by sharp sheet metal

edges. Be careful when placing any sheet metal parts

on such roof.

CAUTION

!

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are

required. Rollers may be used to move unit across a roof.

Level by using unit frame as a reference. See Table 1 and

Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 5.

Refer to rigging instructions on unit.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in

equipment damage.
All panels must be in place when rigging. Unit is not

designed for handling by fork truck.

CAUTION

!

Before setting the unit onto the curb, recheck gasketing on

curb.

C06005

UNIT

MAX WEIGHT

DIMENSIONS

A

B

C

LB

KG

IN

MM

IN

MM

IN

MM

581J---04A

760

345

74.5

1890

38.0

965

33.5

850

581J---05A

895

407

74.5

1890

38.0

965

41.5

1055

581J---06A

930

423

74.5

1890

37.5

955

41.5

1055

NOTES:

1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of

gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 5 -- Rigging Details

581J