581j – Bryant PURON 581J User Manual

Page 36

Advertising
background image

36

Legend and Notes for Table 5

LEGEND:

BD

--- Belt drive

indoor fan motor

BRKR

--- Circuit breaker

CO

--- Convenient outlet

DD

--- Direct drive

indoor fan motor

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

PWRD CO

--- Powered convenient outlet

UNPWR CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and

combination load equipment (refer to NEC Articles 430 and

440), the overcurrent protective device for the unit shall be

fuse or HACR breaker. Canadian units may be fuse or circuit

breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply

voltage is greater than 2%. Use the following formula to de-

termine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.

581J