Table 4 – LEDs

The LEDs on the RTU Open show the status of certain functions

If this LED is on...

Status is...

Power

RTU Open has power

Rx

RTU Open is receiving data from the network segment

Tx

RTU Open is transmitting data over the network segment

DO#

The digital output is active

The

Run and Error LEDs indicate control module and network status

If Run LED shows...

And Error LED shows...

Status is...

2 flashes per second

Off

Normal

2 flashes per second

2 flashes,

alternating with

Run LED

Five minute auto---restart delay after system error

2 flashes per second

3 flashes,

then off

Control module has just been formatted

2 flashes per second

4 flashes,

then pause

Two or more devices on this network have the

same ARC156 network address

2 flashes per second

On

Exec halted after frequent system errors or

control programs halted

5 flashes per second

On

Exec start---up aborted, Boot is running

5 flashes per second

Off

Firmware transfer in progress, Boot is running

7 flashes per second

7 flashes per second, alternating with

Run LED

Ten second recovery period after brownout

14 flashes per second

14 flashes per second,

alternating with

Run LED

Brownout

On

On

Failure. Try the following solutions:
S

Turn RTU Open off, then on.

S

Format RTU Open.

S

Download memory to RTU Open.

S

Replace RTU Open.

NOTE: Refer to Catalog No. TS--5580J--01 for complete

configuration of RTU Open operating sequences. Contact
your Bryant applications engineer for details on
configuration and troubleshooting of connected networks.

Outdoor Air Enthalpy Control

(PNO 33CSENTHSW)

The enthalpy control (33CSENTHSW) is available as a

field--installed accessory to be used with the EconoMi$er2

damper system. The outdoor air enthalpy sensor is part of

the enthalpy control. (The separate field--installed

accessory return air enthalpy sensor (33CSENTSEN) is

required for differential enthalpy control. See Fig. 52.)

Locate the enthalpy control in the economizer next to the

Actuator Motor. Locate two GRA leads in the factory

harness and connect the gray lead labeled “ESL” to the

terminal labeled “LOW”. See Fig. 52. Connect the

enthalpy control power input terminals to economizer

actuator power leads RED (connect to 24V) and BLK

(connect to GND).

7

CTB ECON
(RTU Open: to J2-6)

LOW

GND

24V

Enthalpy
Switch

GRA

BLK

RED

Factory Wiring Harness

PL6-1 (24-V)

PL6-4 (COM)

C11169

Fig. 52 -- Enthalpy Switch (33CSENTHSW) Connections

The outdoor enthalpy changeover setpoint is set at the

enthalpy controller.

Differential Enthalpy Control —

Differential enthalpy control is provided by sensing and

comparing the outside air and return air enthalpy

conditions. Install the outdoor air enthalpy control as

described above. Add and install a return air enthalpy

sensor.