14 Installing the XM Electronic Overspeed Detection System

XM Installation
Requirements

This section describes wire, power, and grounding requirements for an XM
system.

Wiring Requirements

Use solid or stranded wire. All wiring should meet the following specifications:

• 12 to 28 AWG copper conductors without pretreatment; 8 AWG

required for grounding the DIN rail for electromagnetic interference
(emi) purposes

• Recommended strip length 8 millimeters (0.31 inches)

• Minimum insulation rating of 300V

• Soldering the conductor is forbidden

• Wire ferrules can be used with stranded conductors; copper ferrules

recommended

Power Requirements

Before installing your module, calculate the power requirements of all modules
in each chassis. The total current draw through the side connector cannot
exceed 3A. Refer to the specifications for the specific modules for power
requirements.

ATTENTION

See the XM Documentation and Configuration Utility CD
for Hazardous Locations installation drawings. The XM
Documentation and Configuration Utility CD is packaged
with the XM modules.

ATTENTION

A separate power connection is necessary if the total
current draw of the interconnecting modules is greater than
3A.