Installing the XM Electronic Overspeed Detection System 27

XM-220 Terminal Block Assignments

XM-220 Terminal Block Assignments

No.

Name

Description

0

Xducer 1 (+)

Transducer 1 connection

1

Xducer 2 (+)

Transducer 2 connection

2

Buffer 1 (+)

Signal 1 buffered output

3

Buffer 2 (+)

Signal 2 buffered output

4

Switched Buffer (+)

Switched buffered output for use with redundant mode

5

Buffer Power 1 IN

Channel 1 buffer power input
Connect to terminal 6 for positive biased transducer or terminal 21 for
negative biased transducer

6

Positive Buffer Bias

Provides positive (-5V to +24V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) and 22 (CH 2) for positive bias transducers

7

TxD

PC serial port, transmit data

8

RxD

PC serial port, receive data

9

XRTN

1

Circuit return for TxD and RxD

10

Chassis

Connection to DIN rail ground spring or panel mounting hole

11

4-20mA 1 (+)

4-20mA output
300 ohm maximum load

12

4-20mA 1 (-)

13

Chassis

Connection to DIN rail ground spring or panel mounting hole

14

Chassis

Connection to DIN rail ground spring or panel mounting hole

15

Chassis

Connection to DIN rail ground spring or panel mounting hole

16

Xducer 1 (-)

1

Transducer 1 connection

17

Xducer 2 (-)

1

Transducer 2 connection

18

Buffer Common

1

Buffered output return

19

Overspeed/Circuit Fault

Overspeed and circuit fault output signal
Used as input by the XM-442 EODS Relay module

20

Switched Buffer (-)

Switched buffered output for use with redundant mode (inverted signal)

21

Buffer/Xducer Pwr (-)

Provides negative (-24V to +9V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) and 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external
sensors (40mA maximum load)

22

Buffer Power 2 IN

Channel 2 buffer power input
Connect to terminal 6 for positive biased transducer or terminal 21 for
negative biased transducer

23

CAN_High

DeviceNet bus connection, high differential (white wire)

24

CAN_Low

DeviceNet bus connection, low differential (blue wire)

25

+24V Out

Internally connected to 24V In 1 (terminal 44)
Used to daisy chain power if XM modules are not plugged into each other

26

DNet V (+)

DeviceNet bus power input, positive side (red wire)