20ma output parameters – Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual

Page 54

Advertising
background image

Publication GMSI10-UM015B-EN-E - June 2011

54 Configuring the XM EODS

2. Select the relay Number that you want to configure. Relay number 1 is

the on-board relay (circuit fault relay for XM EODS). Numbers 2
through 5 are either relays on the XM-441 Expansion Relay module
when it’s connected to the XM-220 or virtual relays.

3. Enter or select the desired parameters to configure the behavior of the

relay. This includes:

• the number of seconds after an alarm condition has been exceeded

before the relay activates (activation delay)

• the alarm that the relay is monitoring
• the conditions that cause the relay to activate (for example, module

fault, measurement exceeds danger level thresholds)

• whether the relay is latched or failsafe

4. When you are finished, choose Device > Download to Device to

download your changes to the XM-220 module.

4-20mA Output Parameters

Use the Alarm, Relay and 4-20 mA Output tab in the XM-220 Speed Module
Configuration Tool to set up the two 4-20mA output signals (A and B). The
parameters are the same for each output.

To configure the 4-20mA parameters, follow these steps.

IMPORTANT

When configuring Relay 1, make certain to select the
Module fault parameter, the Failsafe relay parameter, and
the Latching parameter to ensure proper functioning of
the XM EODS.

TIP

Refer to Chapter 3 in the XM-220 Dual Speed
Module User Guide for a detailed description of the
configuration parameters.

TIP

Press F1 to display the online help topic for the
current tab or dialog.

Advertising