Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual

Page 28

Advertising
background image

Publication GMSI10-UM015B-EN-E - June 2011

28 Installing the XM Electronic Overspeed Detection System

1

Terminals are internally connected and isolated from the Chassis terminals.

27

DNet V (-)

DeviceNet bus power input, negative side (black wire)

28

24V Common

1

Internally connected to 24V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal

29

4-20mA 2 (+)

4-20mA output
300 ohm maximum load

30

4-20mA 2 (-)

31

Chassis

Connection to DIN rail ground spring or panel mounting hole

32

Chassis

Connection to DIN rail ground spring or panel mounting hole

33

Chassis

Connection to DIN rail ground spring or panel mounting hole

34

Chassis

Connection to DIN rail ground spring or panel mounting hole

35

Chassis

Connection to DIN rail ground spring or panel mounting hole

36

Chassis

Connection to DIN rail ground spring or panel mounting hole

37

Chassis

Connection to DIN rail ground spring or panel mounting hole

38

Chassis

Connection to DIN rail ground spring or panel mounting hole

39

Start

Switch input to activate startup switch (active closed)

40

Switch RTN

Switch return for Start and Reset Relay

41

Reset Relay

Switch input to reset internal relay (active closed)

42

+24V In 2

Connection to secondary external +24V power supply, positive side
Used when redundant power supplies are required

43

24V Common

1

Connection to external +24V power supply, negative side (internally
DC-coupled to circuit ground)

44

+24V In 1

Connection to primary external +24V power supply, positive side

45

24V Common

1

Connection to external +24V power supply, negative side (internally
DC-coupled to circuit ground)

46

Relay N.C. 1

Relay Normally Closed contact 1

47

Relay Common 1

Relay Common contact 1

48

Relay N.O. 1

Relay Normally Open contact 1

49

Relay N.O. 2

Relay Normally Open contact 2

50

Relay Common 2

Relay Common contact 2

51

Relay N.C. 2

Relay Normally Closed contact 2

XM-220 Terminal Block Assignments

No.

Name

Description

Advertising