Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual

Page 43

Advertising
background image

Publication GMSI10-UM015B-EN-E - June 2011

Installing the XM Electronic Overspeed Detection System 43

Channel 1 and Channel 2 Indicator

Startup (Start) Indicator

Relay Indicators

Color

State

Description

No color

Off

• Normal operation within alarm limits on the XM-220

channel.

• No power applied to the module, look at XM-220

Module Status LED.

Yellow

Solid

An alert level alarm condition exists on the channel
(and no transducer fault, tachometer fault, or danger
level alarm condition exists).

Flashing

Tachometer fault (no transducer fault) condition exists
on the XM-220 channel.

Red

Solid

A danger level alarm condition exists on the XM-220
channel (and no transducer fault or tachometer fault
condition exists).

Flashing

A transducer fault condition exists on the XM-220
channel.

Color

State

Description

Yellow

Off

Startup period is not in effect.

Solid

Startup period is in effect.
• XM-220 module may be inhibiting the Tach Fault

alarm status.

• XM-220 module may be monitoring for locked rotor

conditions.

Color

State

Description

Red

Off

On-board relay is not activated.

Solid

On-board relay is activated.

Advertising