Relay parameters – Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual

Page 53

Advertising
background image

Publication GMSI10-UM015B-EN-E - June 2011

Configuring the XM EODS 53

4. When you are finished, choose Device > Download to Device to

download your changes to the XM-220 module.

Relay Parameters

Use the Alarm, Relay and 4-20 mA Output tab in the XM-220 Speed Module
Configuration Tool to configure which alarms the relay is associated with, as
well as the behavior of the relay.

The on-board relay (Relay 1) serves as the circuit fault relay for the overspeed
channel (channel 1). It must be configured for failsafe operation (normally
energized) and latching.

To configure the relay parameters, follow these steps.

1. In the XM-220 Speed Module Configuration Tool, click the Alarm,

Relay and 4-20 mA tab. You will see a screen similar to this.

TIP

Press F1 to display the online help topic for the
current tab or dialog.

IMPORTANT

To ensure proper functioning of the XM EODS, Relay 1 in
each of the XM-220 modules must have the Failsafe relay,
Latching
, and Module fault parameters enabled
(selected).

This checkbox must checked

in order to use the relay.

The activation logic must persist for this

length of time before the relay is activated.

The relay activation logic and what alarm

the relay is to monitor.

The alarm conditions that cause the relay

to activate. More than one can be

checked.

Check the checkbox if the relay is normally

energized. Uncheck the checkbox if the

relay is normally de-energized. This

checkbox must be checked for circuit fault

relay.

Check the checkbox if the relay is to be explicitly
reset (as required in the XM EODS). Uncheck the
checkbox if the relay is to reset itself. This
checkbox must be checked for circuit fault relay.