Configuring the XM EODS 55

1. In the XM-220 Speed Module Configuration Tool, click the Alarm,

Relay and 4-20 mA tab. You will see a screen similar to this.

2. Select the 4-20 mA output (A or B) that you want to configure.

3. Enter or select the desired parameters to define the characteristics of the

4-20mA output signal. This includes:

• the measurement that the 4-20mA output is tracking
• the min and max range of the 4-20mA output signal

4. When you are finished, choose Device > Download to Device to

download your changes to the XM-220 module.

This checkbox must be checked in
order to enable the 4-20mA output.

The measurement and channel that
the 4-20mA output tracks.

The measured value associated with
the 4mA end of the range.

The measured value associated with
the 20mA end of the range.

TIP

Refer to Chapter 3 in the XM-220 Dual Speed
Module User Guide for a detailed description of the
configuration parameters.

TIP

Press F1 to display the online help topic for the
current tab or dialog.