Bendix Commercial Vehicle Systems AD-SP SYSTEM PURGE AIR DRYER 10/04 User Manual

Page 30

Advertising
background image

30

IMPORTANT: The Complaints, Causes and Remedies presented here should not be considered as the only situations possible.

They are only meant to represent the most commonly encountered situations. It may be necessary to perform additional troubleshooting

using the more detailed information presented in service manuals for the specific components.

1. Discharge plugged or restricted

• Connect a temporary discharge line from the

compressor discharge port to the supply reservoir

and re-check the build-up. If the system build-up is

OK then replace the plugged discharge line. If the

build-up is NOT OK, go to next cause.

2. Air pressure trapped between the governor and the

compressor

• Verify the safety valve operation, then remove or

disconnect the governor from the compressor and

check build-up.

• If the build-up is OK, repair or replace the governor or

the line between the governor and the compressor.

• If the build-up is NOT OK, repair or replace the

compressor.

3. Blow Leakage at the Air Dryer Exhaust

• Drain all air from the supply reservoir then remove the

control air line from the air dryer, plug the line and plug

the control port in the air dryer. Re-check build-up.

• If the build-up is OK, repair or replace the governor

or the line between the governor and the air dryer.

• If the build-up is NOT OK, and the temperature is

below 32° F, turn the ignition ON and allow the heater

to warm the air dryer then check the system build-up.

If NOT OK, remove the wire (connector or terminal)

from the air dryer. Using a test light, check the wire

end, or terminal, for battery voltage with the vehicle

ignition ON. If the voltage is OK, repair or replace the

air dryer heater and thermostat. If the voltage is NOT

OK, repair or replace the vehicle wire connected to

the air dryer. Retest build-up.

• If build-up is still NOT OK, or if the temperature

is above 32° F, replace the air dryer purge valve

assembly.

4. Air system leakage

• Build the system pressure to governor cut-out, wait

two (2) minutes for the air dryer purge completion.

Note the pressure on the dash gauges then watch

the dash gauges for two (2) minutes. The leakage is

not to exceed 2 psi in two (2) minutes for truck bus

or tractor (no trailer).

• If the leakage is NOT OK on the gauges, find the

leak(s) in service and park system and repair. Retest

and if the system purge air dryer is in use and still not

OK, repair or replace the dryer.

• If the leakage is OK on the gauges, drain the air

from the supply reservoir, remove the drain cock

and install an air gauge. Build the system air in the

supply reservoir and note the leakage. If OK, continue

checking. If NOT OK, find the leaks and repair.

5. Discharge line leakage

• Apply a soap solution to the cover on the flexible

discharge line, if leakage is noted, replace the line.

• Soap fittings to check for leakage and tighten as

needed.

TESTS COMMON TO MORE THAN ONE COMPLAINT

SD-08-2414 © 2014 Bendix Commercial Vehicle Systems LLC, a member of Knorr-Bremse Group • 9/2014 • All rights reserved.

Log-on and Learn from the Best

On-line training that's available when you are 24/7/365.

Visit www.brake-school.com.

Advertising
This manual is related to the following products: