Hood box – Bryant 580F User Manual

Page 18

Advertising
background image

18

B. Optional EconoMi$er+

See Fig. 16 for EconoMi$er+ component locations.

NOTE: These instructions are for the factory-installed optional
EconoMi$er+ only. Refer to the accessory EconoMi$er+
installation instructions when field installing an EconoMi$er+
accessory.

1. To remove the existing unit filter access panel, raise

the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 17.

2. The box with the EconoMi$er+ hood components is

shipped in the compartment behind the EconoMi$er+.
The EconoMi$er+ does not have to be removed to
retrieve the hood box. Remove the screw holding the
hood box bracket to the top of the EconoMi$er+. Slide
the hood box out of the unit. See Fig. 18.

IMPORTANT: If a power exhaust accessory will be installed
on the unit, the hood shipped with the unit will not be used
and must be discarded. Save the aluminum filter for use in
the power exhaust.

3. The indoor coil access panel will be used as the top of

the hood. Remove the screws along the bottom of the
indoor coil access panel. See Fig. 19.

4. Swing out the indoor coil access panel and insert the

hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
the screws provided to attach the hood sides to the
unit. See Fig. 20.

5. Remove the shipping tape holding the EconoMi$er+

barometric relief damper in place.

6. Insert the hood divider between the hood sides. See

Fig. 20. Secure hood divider with 2 screws on each
hood side. The hood divider is also used as the bottom
filter rack for the aluminum filter.

7. Open the filter clips which are located underneath

the hood top. Insert the aluminum filter into the
bottom filter rack (hood divider). Push the filter into
position past the open filter clips. Close the filter clips
to lock the filter into place. See Fig. 21.

8. Caulk the ends of the joint between the unit top panel

and the hood top. See Fig. 19.

9. Replace the filter access panel.

10. Install all EconoMi$er+ accessories. EconoMi$er+ wiring

is shown in Fig. 22.

Barometric flow capacity is shown in Fig. 23. Outdoor air
leakage is shown in Fig. 24. Return air pressure drop is
shown in Fig. 25.

FILTER ACCESS PANEL

INDOOR COIL ACCESS PANEL

Fig. 17 — Typical Access Panel Locations

Hood

Box

HOOD BOX
BRACKET

Fig. 18 — Hood Box Removal

SIDE
PANEL

INDOOR
COIL
ACCESS
PANEL

INDOOR
COIL
ACCESS
PANEL

CAULK
HERE

TOP
SIDE
PANEL

Fig. 19 — Indoor Coil Access Panel Relocation

ECONOMI$ER+
PLUG

ECONOMI$ER+
CONTROLLER
(UNDER COVER)

OUTDOOR
AIR HOOD

HOOD
SHIPPING
BRACKET

ECONOMI$ER+
CONTROLLER
LABELS

GEAR
DRIVEN
DAMPER

OUTDOOR AIR
TEMPERATURE
SENSOR

BAROMETRIC
RELIEF
DAMPER

Fig. 16 — EconoMi$er+ Component Locations