Table 8 — Fan Rpm at Motor Pulley Settings*

*Approximate fan rpm shown.

†Indicates standard motor and drive package.

**Indicates alternate motor and drive package.

††Indicates high-static motor and drive package.

Table 9 — Evaporator-Fan Motor Efficiency

NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.

UNIT 580F

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

090,091†

840

815

790

765

740

715

690

665

635

615

590

090,091**

935

910

885

860

835

810

785

760

735

710

685

090,091††

1080

1025

1007

988

970

952

933

915

897

878

860

102,103†

935

910

885

860

835

810

785

760

735

710

685

102,103††

1080

1025

1007

988

970

952

933

915

897

878

860

120,121†

935

910

885

860

835

810

785

760

735

710

685

120,121**

1085

1060

1035

1010

985

960

935

910

885

860

835

120,121††

1130

1112

1087

1062

1037

1012

987

962

937

912

887

862

830

150,151†

1080

1060

1035

1015

990

970

950

925

905

880

860

150,151**

1130

1112

1087

1062

1037

1012

987

962

937

912

887

862

830

UNIT
580F

MOTOR EFFICIENCY

(%)

090-121

80

150,151

87

Fig. 34 — Typical Belt-Drive Motor Mounting