TROUBLESHOOTING

I. ECONOMI$ER+ TROUBLESHOOTING

The EconoMi$er+ control has built-in diagnostics. The con-
trol can detect and display 10 different diagnostic codes as
shown in Table 37. The user can also use the integrated dis-
play to check the status of all the inputs and outputs and run
the manual control mode to check the operation of the
EconoMi$er+ and compressors.

Table 37 — EconoMi$er+ Error Codes

LEGEND

*If there is a RAM failure DS1+DS3/DS2+DS4 will alternately flash.

†If there is a ROM failure DS1+DS2/DS3+DS4 will alternately flash.

A. Error Code 1 — SAT Sensor Failure

Error Criteria

An SAT Sensor Failure error will occur if the sensor is
shorted or faulty. If the measured temperature reads below
–40 F or above 250 F an error will occur.

Required Action

If an error occurs, then the control will default to Mode 2
compressor stage control where Y1 and Y2 have direct con-
trol of the compressors. Use of free cooling is disabled and
the EconoMi$er+ will be set to the minimum damper posi-
tion for either the occupied or unoccupied mode of operation.
Replace sensor if faulty.

Reset Method

The error will automatically reset after the value has
returned to a normal level. The alarm has to be cleared from
the display in the Setup mode or a power reset.

B. Error Code 2 — RAT Sensor Failure

Error Criteria

The RAT Sensor failure error is only applicable the unit has
been configured for EconoMi$er+ changeover methods 3 (dif-
ferential dry bulb) or 5 (differential humidity). For other
modes it should be ignored. If the sensor is shorted or faulty,
then the measured temperature will be below –40 F or above
250 F and the error will occur.

Required Action

If this error occurs, then change the default EconoMi$er+
changeover control to method 2 (dry bulb changeover con-
trol) or replace sensor.

Reset Method

This error will automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode.

C. Error Code 3 — OAT Sensor Failure

Error Criteria

An OAT Sensor Failure error occurs if the sensor is shorted
or faulty, then the measured temperature will be below –40
F or above 250 F.

Required Action

— If this error occurs disable the economizer and set the
economizer to the minimum economizer position.

Reset Method

This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.

D. Error Code 4 — ORH (Outdoor Relative Humidity) Sensor
Failure

Error Criteria

If the unit is configured for economizer changeover type 3 or
4, and the input signal is less than 2 mA or greater than
22 mA, then the sensor is faulty and an error will occur.

Required Action

If this error occurs, switch the EconoMi$er+ to dry bulb
changeover control.

Reset Method

This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.

E. Error Code 5 — IRH (Indoor Relative Humidity) Sensor
Failure

Error Criteria

This error occurs if the unit is configured for EconoMi$er+
changeover type 5 and the input signal is less than 2 mA or
greater than 22 mA (faulty sensor).

Required Action

If this error occurs, switch the EconoMi$er+ to differential
dry bulb changeover control.

Reset Method

This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.

F. Error Code 6 — IAQ Sensor Failure

Error Criteria

This error occurs if the unit is configured for IAQ demand
ventilation control and the input signal is less than 2 mA or
greater than 22 mA (faulty sensor).

Required Action

If this error occurs, disable the IAQ control routine and
default to the standard EconoMi$er+ minimum position.

Reset Method

This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.

G. Error Code 7 — Y2 On with Y1 Off

Error Criteria

This error occurs if Y2 is turned on and Y1 is off. This indi-
cates that there is a wiring error at the thermostat connec-
tions. This alarm should be ignored for the first 20 seconds of
operation so that it does not conflict with the special produc-
tion test mode.

NO.

DESCRIPTION

CRITERIA

1

SAT Sensor Failure

Temperature <–40 F or Greater Than 250 F

2

RAT Sensor Failure

Temperature <–40 F or Greater Than 250 F

3

OAT Sensor Failure

Temperature <–40 F or Greater Than 250 F

4

ORH Sensor Failure

Read Less Than 2 mA or Greater Than 22 mA

5

IRH Sensor Failure

Read Less Than 2 mA or Greater Than 22 mA

6

IAQ Sensor Failure

Read Less Than 2 mA or Greater Than 22 mA

7

Y2 On Y1 Off

Wiring Error

8

Micro Fails E2 Tests

Hardware/Software Check

*

Micro Fails RAM Test

Hardware/Software Check

Micro Fails ROM Tests

Hardware/Software Check

IAQ

Indoor Air Quality

IRH

Indoor Relative Humidity

OAT — Outdoor Air Temperature
ORH — Outdoor Relative Humidity
RAT — Return Air Temperature
SAT

Supply Air Temperature