Fig. 36 — economi$er+ controller board – Bryant 580F User Manual

Page 53

Advertising
background image

53

tens digit and the DS4 LED will then display the ones digit.
For example to display 54, the DS3 LED will flash 1 group of
5 at a high flash rate to indicate 50, and then follow with 4
flashes (DS4) at 1-second intervals to complete the display of
the number 54.

NOTE: Do not try to count the “5 Fast Flashes” individually,
but instead count how many groups of 5 flashes were
displayed. In this case, 1 group of 5 flashes, plus the 4 flashes
at 1 second results in the value of 54.

To read the display again, push the READ/ADJUST (#1) but-
ton and the sequence will repeat as many times as needed.

To advance to the next setup point, push the ADVANCE/
MANUAL (#2) button. The controller will cycle through all
the setup channels (Table 34) and then the I/O channels
(Table 35) and then back to the first setup channel.

NOTE: The user can only advance forward, not reset to #1 or go
backwards. Cycling the EconoMi$er+ power will reset the item
number (but not the item value) to item #1.

In the Read mode for setup variables, the LEDs will not turn
on steady; the LEDs will always flash. Steady-on indicators
are reserved for the configuration modes. No data is modified
in the Read mode. The controller will always remain at the
last read number even if reset back to normal operation.

NOTE: To enter another mode, the user first must exit the
Read mode.

If no button is pushed in 10 minutes, Read mode will auto-
matically be exited. Also, if the READ/ADJUST (#1) and
ADVANCE/MANUAL (#2) buttons are pushed and held for
more than 3 seconds, then Read mode will be exited to Run
mode. While in the Read mode, the controller will continue to
operate with normal unit control.

Y1

Y2

G

OCC

24V

1

J1

5

Y1 (cool 1)

Y2 (cool 2)

G (fan)

OCC

24 VAC

THERMOST

A

T

INPUTS

Occupied/unoccupied
I/O support dry circuit
contact (min 24 mA I)

POWER

SUPPLY

2-10 VDC

ECONOMIZER

CONTROL

J2

1

5

CNT

24V

24V

24

V

A

C

24

V

A

C

Control

SA

T

OA

T

RA

T

IRH

VRF

ORH

VRF

IAQ

MIN

VRF

IAQ

(4-20ma)

min

(10K

pot)

ORH

(4-20

ma)

V

ref

V

ref

V

ref

IRH

(4-20

ma)

RA

T

(10k

thermistor)

OA

T

(10k

thermistor)

SA

T

(10k

thermistor)

J3

1

17

ANALOG INPUTS

4-20 mA external powered between signal and ground
4-20 mA loop powered between 24 VDC and signal

Relays rated at 24 VAC 3A
and traces for 8A.
NOTE: For 1 and 2 stage
cooling, 2 stages of power
exhaust will be used.
For 3 cooling stages, only 1
stage of power exhaust will be
used, and for 4 stages no power
exhaust will be controlled
directly by the control.

OUTPUT

RELA

YS

C1

C2

24V

24V

24V

C3

C4

24 VAC

24 VAC

24 VAC

CP1

CP2

EX2/CP3

EX1/CP4

J4

READ/

ADJUST

ADVANCE

MANUAL

DS1

DS2

SETPOINT DISPLAY

DS3

DS4

date or serial no

RED YELLOW

GREEN

PUSH BUTTONS

# 1

# 2

Fig. 36 — EconoMi$er+ Controller Board