Table 35 — input/output channels – Bryant 580F User Manual

Page 55

Advertising
background image

55

Table 34 — Configuration Variables (Read and Setup Modes)

LEGEND

NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible.
SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to
reset alarms.

Table 35 — Input/Output Channels

NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible for reading.

ADJUST MODE — Only channels 1-5 will be accessible.
MANUAL MODE — Only channels 1-5 will be accessible.

NO.

SETUP POINTS

(viewable and adjustable)

UNITS

MINIMUM

VALUE

MAXIMUM

VALUE

FACTORY

SETTING

INC

COMMENTS

1

Supply Air Temperature Setpoint

F

40 F

65 F

55 F

1 F

Leaving Air Temperature Control Point

2

Occupied Minimum Economizer
Position

%

Item 15 +1%

100%

15%

1%

Min Econo Position (occupied mode)

3

Unoccupied Minimum Economizer
Position

%

1%

100%

5%

1%

Min Econo Position (unoccupied mode)

4

Economizer Maximum Position

%

1%

100%

100%

1%

Maximum Econo Position

5

Economizer Type

1

3

2

1

1 = Vent Only, 2 = Proportional,
3 = 3 Position

6

Economizer Changeover Type

1

5

2

1

1 = Switch, 2 = Outdoor Dry Bulb,
3 = Diff Dry Bulb, 4 = Outdoor Enthalpy,
5 = Diff Enthalpy

7

Economizer Changeover Setpoint
(mode 2)

F

45 F

70 F

65 F

1 F

For Outdoor Changeover

8

Economizer Changeover Setpoint
(mode 3)

1

4

1

1

Outdoor Enthalpy Changeover Setpoint
1 = A, 2 = B, 3 = C, 4 = D

9

No. of compressors

1

4

2

1

1, 2, 3, or 4

10

Compressor Sequencing

1

4

1

1

1 = DC-Sensible, 2 = DC-Latent,
3 = LAT-Sensible, 4 = LAT-Latent

11

Power Exhaust Stage 1 Activation

%

1%

Item 12 -5%

25%

1%

Economizer Position

12

Power Exhaust Stage 2 Activation

%

Item 11 +1%

100%

50%

1%

Economizer Position (> stage 1)

13

Unoccupied Configuration

1

3

3

1

1 = No Unoccupied Cooling,
2 = Unoccupied Free Cooling,
3 = Unoccupied Free & Mech Cooling

14

Compressor Lockout Temperature

1 F

65 F

45 F

1 F

Compressor Operation

15

IAQ Min Economizer Position
Setpoint

%

1%

Item 2 +1%

5%

1%

Min IAQ Position for VOC Emissions

16

IAQ Enable

1

2

1

1

1 = Disabled, 2 = Enabled

17

Outdoor IAQ Reference

PPM/10

1 PPM/10

100 PPM/10

40 PPM/10

1 PPM/10 Outdoor Reference IAQ Level

18

IAQ Lower Limit Control Point
Differential

PPM/10

1 PPM/10

Item 19 -1

PPM/10

60 PPM/10

1 PPM/10

Differential Lower Limit Indoor
IAQ Level

19

IAQ Upper Limit Control Point
Differential

PPM/10

Item 18 +1

PPM/10

200 PPM/10

140 PPM/10

1 PPM/10

Differential Upper Limit Indoor
IAQ Level

20

1st Most Recent Error/Reset

1

8

Used in Setup Mode to Reset Alarms

21

2nd Most Recent Error (read only)

1

8

Not Displayed in Setup Mode

22

3rd Most Recent Error (read only)

1

8

Not Displayed in Setup Mode

23

4th Most Recent Error (read only)

1

8

Not Displayed in Setup Mode

24

5th Most Recent Error (read only)

1

8

Not Displayed in Setup Mode

DC

Direct Control

IAQ

Indoor Air Quality

LAT — Leaving Air Temperature Compensated Control
VOC — Volatile Organic Compounds

NO.

I/O POINTS

UNITS

MINIMUM VALUE

MAXIMUM VALUE

INC

COMMENTS

1

C1 Output

Off

On

Compressor 1

2

C2 Output

Off

On

Compressor 2

3

C3 Output

Off

On

Compressor 3/Power Exhaust 2

4

C4 Output

Off

On

Compressor 4/Power Exhaust 1

5

Economizer Damper Output

%

1 F

100 F

1%

Damper Commanded Position

6

Supply Air Temperature

F

1 F

150 F

1 F

Supply Air Temperature

7

Outdoor Air Temperature

F

1 F

150 F

1 F

Outdoor Air Temperature

8

Return Air Temperature

F

1 F

150 F

1 F

Return Air Temperature

9

Indoor Relative Humidity

%

1%

100%

1%

Return Air Relative Humidity

10

Outdoor Relative Humidity

%

1%

100%

1%

Outdoor Air Relative Humidity

11

Indoor Air Quality

PPM

1 PPM/10

200 PPM/10

10 PPM

Indoor Air Quality (/10)

12

Remote Minimum Position

%

1%

100%

1%

Remote Minimum Pot Position

13

Y1 Status

Open

Close

Thermostat Y1 Status

14

Y2 Status

Open

Close

Thermostat Y2 Status

15

G Status

Open

Close

Indoor Fan Status

16

Occ Status

Open

Close

Remote Occupied Status