IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED

Adjust evaporator-fan speed to meet jobsite requirement.

Table 8 shows fan rpm at motor pulley settings and Table 9
shows motor efficiencies. Table 10 shows motor performance.
Refer to Fan Performance Tables 11-30 to determine fan
speed settings. Fan motor pulleys are factory set for speed
shown in Tables 1A and 1B.

To change fan speed:

1. Shut off unit power supply and install lockout tag.
2. Loosen belt by loosening fan motor mounting plate

nuts (see Fig. 33 and 34).

3. Loosen movable pulley flange setscrew (see Fig. 35).
4. Screw movable flange toward fixed flange to increase

fan speed and away from fixed flange to decrease fan
speed. Increasing fan speed increases load on motor.
Do not exceed maximum speed specified in Tables 1A
and 1B.

5. Set movable flange at nearest flat of pulley hub and

tighten setscrew (see Tables 1A and 1B for speed
change for each full turn of pulley flange).

To align fan and motor pulleys:

1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from

mounting plate.

To adjust belt tension (see Fig. 33 and 34):

1. Loosen fan motor mounting plate nuts.
2. Units 090-103 — Slide motor mounting plate away

from fan scroll for proper belt tension (

1

/

2

-in.

deflection with 5 to 10 lb of force) and tighten mount-
ing nuts (see Fig. 33).
Units 120-151 — Slide motor mounting plate down-
ward to tighten belt tension. (

1

/

2

-in. deflection with

5 to 10 lb of force.) Secure motor mounting plate nuts.
See Fig. 34.

3. Adjust bolt and nut on mounting plate to secure

motor in fixed position.

Realign fan and motor pulleys:

1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from

mounting plate.

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL

RANGE (ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Interface with Standard
Building Control System

Proportional

Any

4-20 mA

0-2000

1000

50

2

Proportional

Any

7-20 mA

0-2000

1000

50

3

Exponential

Any

4-20 mA

0-2000

1100

50

4

Economizer

Proportional

15

4-20 mA

0-1100

1100

50

5

Proportional

20

4-20 mA

0- 900

900

50

6

Exponential

15

4-20 mA

0-1100

1100

50

7

Exponential

20

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/ Loading Docks

Proportional

4-20 mA

0-2000

700

50

ppm — Parts Per Million

MOTOR MOUNTING
PLATE NUTS

Fig. 33 — Typical Belt-Drive Motor Mounting

for Sizes 090-103