Bryant 580F User Manual

Page 57

Advertising
background image

57

5. Use button #2 (ADVANCE/MANUAL) to advance to

configuration point number 2, Occupied Min.

6. Verify the configuration point by pushing button #1.

The red LED should flash twice to indicate point 2,
and then the green LEDs will flash the current setting.

NOTE: Since the occupied minimum position MUST be 1
greater than the IAQ minimum position (item 15), the IAQ
minimum position must be changed first. (IAQ min has a
default value of 5%, which is higher than the 2% value in this
example.)

7. Use button #2 (ADVANCE/MANUAL) to get to config-

uration point 15 (IAQ Minimum Position).

NOTE: Before performing Step 8, be ready to push button #1;
there is a limited time window that can easily be missed when
the DS3 green LED comes on, and again when the DS4 green
LED comes on.

8. Verify the configuration point by pushing button #1.

The red LED should flash 15 times to indicate point
15, then the green LEDs will flash the current
setting.

9. Next, the green DS3 LED will turn on steady for

2 seconds. During this time, do NOT do anything so
that the position defaults to 0.

10. The DS3 LED will turn off and the green DS4 LED

will go on steady for 2 seconds. During this time,
push button #1 once to set the point to 1%.

11. Wait until the green LEDs turn off then verify the

setting by pushing button #1 to read the value. DS3
should not blink, and DS4 should blink once.

12. Now configure the Occupied Minimum Position to

2%. Use button #2 (ADVANCE/MANUAL) to get to
configuration point 2.

NOTE: Before performing Step 13, be ready to push button #1;
there is a limited time window that can easily be missed when
the DS3 green LED comes on, and again when the DS4 green
LED comes on.

13. Verify the configuration point by pushing button #1.

The red LED should flash twice to indicate point 2,
then the green LEDs will flash the current setting.

14. Next, the green DS3 LED will turn on steady for

2 seconds. During this time, do NOT do anything so
that the position goes to 0.

15. The DS3 LED will turn off and the green DS4 LED

will go on steady for 2 seconds. During this time,
push button #1 twice to set the point to 2%.

16. Wait until the green LEDs turn off then verify the

setting by pushing button #1 to read the value. DS3
should not blink, and DS4 should blink twice.

NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in
Table 34) are dependent upon other items. Before attempting
to change one of these items, be sure to check the value of the
item it depends upon (as described in Example 2 above).

IMPORTANT: During SETUP MODE, changes are allowed
when the DS3 LED and DS4 LED are lit for 2 seconds (as
described in Example 1 and 2 above). During this time, if
button #1 is pushed to change one position and not the other,
the value for that one position will change and the other will
default to zero (unless a dependency prevents the zero). How-
ever, if button #1 is not pushed at all during the 2 seconds
that the green LEDs are lit, the configuration item will not
change.

F. Manual Mode

Manual mode is used to control the status of I/O channels for
use in troubleshooting. See Table 35.

Enter the Manual mode by holding down the ADVANCE/
MANUAL (#2) button for at least 3 seconds until all LEDs
flash and then the red LED comes on steady.

NOTE: A user can only enter the Manual mode from the Run
mode, which is entered by pushing buttons #1 and #2 for at
least 3 seconds.

All EconoMi$er+ control outputs are turned off. “I/O Inputs”
1-5 can be adjusted even if the unit is in operation.

In manual mode, the yellow DS2 LED flashes once to indicate
the I/O channel. See Table 35. If the value is less than 5, the
yellow DS2 LED will count out the value using 1-second
flashes. If the value is greater than 4, the yellow DS2 LED
will count out groups of 5 at a high flash rate and then follow
with the additional value at a flash rate of once per second.
For example a flash of 1 indicates Compressor Relay Output 1.

Push READ/ADJUST button (#1) to read the value. The yel-
low LED will flash the I/O Channel number being viewed.

Once the channel number is displayed it will then turn on
the appropriate green LED (DS3 or DS4) to indicate the sta-
tus of the output. For relay outputs if the DS3 LED is on,
then the output is on. If DS4 is on, then the output is off. The
green DS3 and DS4 LEDs will remain on for about 2 seconds
and if during this time the READ/ADJUST (#1) button is
pushed, then the output will toggle to the alternate state. To
change again, push the READ/ADJUST button and repeat
the test or change the status of the output. As an example,
for channel 5 (EconoMi$er+ control damper motor) use the
READ/ADJUST button to toggle the motor from open to
close in %.

At any time, the ADVANCE/MANUAL (#2) button can be
used to advance to the next SET I/O. To exit the mode, push
and hold the READ/ADJUST and ADVANCE/MANUAL but-
tons (#1 and #2) for more than 3 seconds.

NOTE: After exiting the Manual mode, the controller will re-
initialize and start with all outputs off.

G. Error Mode

The error mode is used to indicate that an error has occurred
The error is indicated by LED #1 red and #2 yellow are on
steady.

Enter the RUN mode by pushing the READ/ADJUST and
ADVANCE/MANUAL buttons (#1 and #2) for at least 3 sec-
onds until all LEDs flash. Next, push and release button #1
to enter the Read mode. Then push button #2 to advance to
item 20 (“first most recent error”). Determine the error by
reading the value in items 20 to 24 and referring to the Trou-
bleshooting section.

Once the error has been fixed, press buttons #1 and 2 for at
least 3 seconds to exit Read mode. All LEDs will flash.

Enter Setup mode by pressing the READ/ADJUST button
(#1) for at least 3 seconds. All LEDs will flash. Push the
ADVANCE/MANUAL button (#2) to advance to item 20.
Push READ/ADJUST to read item 20.

To reset the error code while the green DS4 LED is on, press
the READ/ADJUST button (#1) once. In addition to resetting
the error mode, this will erase all error codes. Cycling the
power will also erase the error code.