Table 25 — Fan Performance 580F102,103 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*

LEGEND

*Motor drive range: 860 to 1080 rpm. All other rpms require field-

supplied drive.

NOTES:

1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2550

550

0.69

647

625

0.92

860

692

1.17

1095

754

1.45

1349

811

1.74

1623

2600

558

0.73

677

632

0.96

894

698

1.21

1131

759

1.49

1388

816

1.78

1664

2700

574

0.80

742

645

1.03

964

710

1.29

1207

770

1.58

1469

826

1.88

1749

2800

589

0.87

811

659

1.11

1039

723

1.38

1287

782

1.67

1554

837

1.97

1839

2900

605

0.95

885

673

1.20

1119

736

1.47

1372

794

1.76

1644

848

2.07

1933

3000

621

1.03

963

688

1.29

1204

749

1.57

1463

806

1.87

1740

859

2.18

2033

3100

637

1.12

1046

702

1.39

1293

762

1.67

1558

818

1.97

1840

871

2.29

2139

3200

654

1.22

1135

717

1.49

1388

776

1.78

1658

831

2.09

1946

882

2.41

2249

3300

670

1.32

1228

732

1.60

1488

789

1.89

1764

843

2.21

2057

894

2.54

2365

3400

686

1.42

1328

747

1.71

1593

803

2.01

1876

856

2.33

2174

907

2.67

2488

3500

703

1.54

1433

762

1.83

1705

817

2.14

1993

870

2.46

2297

919

2.81

2616

3600

720

1.66

1543

777

1.95

1822

832

2.27

2116

883

2.60

2425

932

2.95

2750

3700

736

1.78

1660

793

2.09

1944

846

2.41

2245

896

2.75

2560

944

3.10

2889

3750

745

1.85

1721

801

2.15

2008

853

2.48

2312

903

2.82

2630

951

3.18

2962

3800

753

1.91

1783

808

2.22

2074

861

2.55

2380

910

2.90

2701

957

3.26

3036

3900

770

2.05

1912

824

2.37

2209

875

2.70

2522

924

3.05

2848

970

3.42

3189

4000

787

2.20

2047

840

2.52

2351

890

2.86

2669

938

3.22

3002

984

3.59

3348

4100

804

2.35

2189

856

2.68

2499

905

3.03

2824

952

3.39

3162

4200

821

2.51

2338

872

2.85

2655

920

3.20

2986

967

3.57

3331

4250

829

2.59

2415

880

2.93

2735

928

3.29

3069

974

3.66

3417

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2550

865

2.05

1914

916

2.38

2223

964

2.73

2547

1010

3.10

2888

1054

3.48

3243

2600

869

2.10

1957

920

2.43

2267

968

2.78

2593

1014

3.15

2935

1058

3.53

3292

2700

879

2.19

2046

929

2.53

2360

976

2.88

2689

1022

3.25

3035

1066

3.64

3395

2800

889

2.29

2140

938

2.64

2458

985

2.99

2791

1030

3.37

3140

2900

899

2.40

2239

948

2.75

2561

994

3.11

2898

1039

3.49

3250

3000

910

2.51

2343

958

2.86

2670

1004

3.23

3011

1048

3.61

3366

3100

921

2.63

2453

968

2.98

2783

1013

3.35

3128

3200

932

2.75

2569

978

3.11

2903

1023

3.49

3252

3300

943

2.88

2690

989

3.25

3029

1033

3.63

3382

3400

954

3.02

2816

1000

3.39

3159

3500

966

3.16

2950

1011

3.54

3297

3600

978

3.31

3088

1022

3.69

3442

3700

990

3.47

3233

3750

996

3.55

3308

3800

1002

3.63

3385

3900

4000

4100

4200

4250

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor