Zone control input, Tekmar net, Device (tn1 / tn2) – tekmar 363 Universal Reset Control Installation User Manual

Page 19: 10k 2 sensor, Unoccupied switch, Step five testing the wiring, Test the sensors, Test the power supply, Test the powered inputs mixing demand

Advertising
background image

19 of 40

Copyright © D 363 -

12/08

Zone Control Input

If an external tekmar Zone Control is used, connect the wire from the
Com Sen terminal on the Zone Control to the Com terminal (20) on the
363. Connect the

Zo Out terminal on the Zone Control to the 10K 1

terminal (21) on the 363.

Note: The wires from the Zone Control are polarity sensitive. The
communication does not operate correctly if the wires are reversed.

tekmar Net

TM

Device (tN1 / tN2)

A Room Temperature Unit (RTU) 062 or 063, or a Remote Display
Module (RDM) 040 may be connected to the

tekmar Net

TM

(tN1 / tN2)

input. Connect the

Com terminal from the appropriate device to the

Com terminal (17) on the 363. Connect the tN1 or tN2 terminal from the
appropriate device to the

tN1 / tN2 terminal (19) on the 363.

Note: The wires from the RTU and the RDM are polarity sensitive. The
tN1 / tN2 device does not operate correctly if the wires are reversed.

10K 2 Sensor

Either a DHW Sensor 071 or a Storage Tank Sensor 071 can connect
to the

10K 2 input. Connect the two wires from the appropriate sensor

to the

Com and 10K 2 terminals (17 and 18).

UnOccupied Switch

If an external timer (tekmar Timer 03

2) or switch is used, connect the

two wires from the external switch to the

Com and UnO Sw terminals

(20 and 22). When these two terminals are shorted together, the
control registers an UnOccupied signal.

Note: The setback override in the schedule menu of the control overrides
any external signal that is present on the UnOccupied Switch terminals.

STEP FIVE

TESTING THE WIRING

Each terminal block

must be unplugged from its header on the control before power is applied for testing. To remove the terminal block,

pull straight down from the control.

The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly
trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 - 300
V (ac) and at least 0 - 2,000,000 Ohms, is essential to properly test the wiring
and sensors.

Test the Sensors

In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer with a
surface temperature probe is recommended for ease of use and accuracy.
Where a digital thermometer is not available, a spare sensor can be
strapped alongside the one to be tested and the readings compared. Test
the sensors according to the instructions in the Data Brochure D 070.

Test the Power Supply

Make sure exposed wires and bare terminals are not in contact with other
wires or grounded surfaces. Turn on the power and measure the voltage
between the N and L terminals (6 and 7) using an AC voltmeter, the
reading should be between 108 and 132 V (ac).

Test the Powered Inputs

Mixing Demand

If a mixing demand is used, measure the voltage between the

Mix

Demand terminals (1 and 2). When the mixing demand device calls for
heat, you should measure between 20 and 260 V (ac) at the terminals.
When the mixing demand device is off, you should measure less
than 5 V (ac).

17

18

Com

10K

2

tN1/

tN2

19

Item

Menu

UnOcc 1

°F

View

Heat

17

18

Com 10K

2

20

21

Com

10K

1

UnO

Sw

22

Timer Switch

Com
Sen

Zo

Out

tekmar 363

Zone Control

20

21

10K

1

Com

V

V

6

7

N

L

Power

108 to 132 V (ac)

V

23

24

Com

Mix

Boil

25

26

Out

V

V

1

2

Mix

Demand

20 to 260 V (ac)

Advertising