tekmar 363 Universal Reset Control Installation User Manual

Page 26

Advertising
background image

26 of 40

Copyright © D 363 -

12/08

363 Adjust Menu (3 of 5)

Occ

UnOcc

35 to 100˚F
(2 to 38˚C)

Default = 70

°F (21°C)

The desired room air temperature during an
Occupied period for the boiler zone(s).

Note: There

is only a

±3°F adjustment in the LTD access level.

DIP switch =

Characterized Heating Curve

35 to 100˚F
(2 to 38˚C)

Default = 65

°F (18°C)

OFF, 0:20 to 8:00 Hr.

Default = OFF

0 to 50˚F
(0 to 28˚C)

Default = 15

°F (8°C)

The desired room air temperature during an
UnOccupied period for boiler zone(s).

DIP switch =

Characterized Heating Curve

DIP switch =

Setback

The

maximum length of morning boost.

DIP switch =

Characterized Heating Curve

DIP switch =

Setback

10K 1

≠ Boil

The amount that the boiler supply temperature
will be reduced when the control is in an
UnOccupied mode.

DIP switch =

Reset Ratio

DIP switch =

Setback

The type of terminal units that are being used for
the boiler side of the system.

DIP switch =

Characterized Heating Curve

The design indoor air temperature used in the
heat loss calculation for the boiler system.

DIP switch =

Characterized Heating Curve

The starting water temperature used in the reset
ratio calculation for the boiler supply.

DIP switch =

Reset Ratio

The design supply temperature used in the heat
loss calculation for the boiler system.

The maximum temperature allowed for the boiler
target temperature.

The minimum temperature allowed for the boiler
target temperature.

35 to 100˚F
(2 to 38˚C)

Default = 70

°F (21°C)

35 to 150˚F
(2 to 66˚C)

Default = 70

°F (21°C)

70 to 220˚F
(21 to 104˚C)

Default = 190

°F (88°C)

120 to 225˚F, OFF
(49 to 107˚C, OFF)

Default = 210

°F (99°C)

OFF, 80 to 180˚F
(OFF, 27 to 82˚C)

Default = 140

°F (60°C)

B1

B1

A

B1

A

B1

B1

B1

B1

B1

HRF1 (Heavy), HRF2
(Light), (Fan-) COIL,
CONV (ector), RAD
(iator), BASE (board)

Default = CONV

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER