Misc. menu, Rtus 062 & 063 – tekmar 363 Universal Reset Control Installation User Manual

Page 29

Advertising
background image

29 of 40

Copyright © D 363 -

12/08

Room Temperature Units (RTUs) 062 and 063

A single RTU may be connected to the Universal Reset Control 363 in order to provide the control with
indoor temperature feedback for the mixing side of the heating system (Refer to Essay E 002). When using
an RTU, several items related to the mixing side of the heating system are no longer available in the control’s
User Interface. These items are available only in the RTU’s User Interface. Also, the number of items that
are available on the RTU depends on the type of RTU that is connected to the control.

The access level that is to be used by the control.

DIP switch =

Unlock

363 Misc (Miscellaneous) Menu (1 of 1)

˚F, ˚C

Default =

°F

OFF, 30 sec, ON

Default =

ON

ADV, INST, USER, LTD

Default = INST

The units of measure that all of the temperatures are to be
displayed in by the control.

The operating mode for the back lighting on the LCD as well
as the time of keypad inactivity until the control automatically
returns to the default display.

BACKLITE = OFF

(returns after 10 seconds)

BACKLITE = 30 sec

(returns after 30 seconds)

BACKLITE = ON (returns after 90 seconds)

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

363 RTU View Menu (1 of 1)

Current room air temperature.

RTU SENS = AIR

- - -, 14 to 167˚F
(-10 to 75˚C)

Target room air temperature.

RTU SENS = AIR

- - -, 35 to 100˚F
(2 to 38˚C)

Current outdoor air temperature.

-67 to 149˚F
(-55 to 65˚C)

Current slab (floor) sensor temperature.

REMOTE 3 = SLAB

-58 to 167˚F
(-50 to 75˚C)

• •

D3

D3

D3

Section

LT

D

INST ADV

USER

RTU 062

RTU 063

Range

Access
Level

Description

Item Field

Item

Menu

UnOcc 1

°

F

View

Heat